The estimated drop exceeds the design limit of 3.0%. Voltage at the load lands at roughly 222.1 V.
lost along the circuit
Enter a circuit's current, cable length and cross-section, and material to see the voltage drop in volts and as a percentage.
Current-carrying capacity, temperature, installation method, grouping, protection, short-circuit withstand, and local codes also need checking. Treat this as a design estimate, not installation approval.
Start with the circuit type and the load.
The length entered is one-way only; the return path is factored into the calculation.
The limit is adjustable because design criteria and codes vary by country, circuit, and application.
Resistance is approximately corrected for temperature. Reactance is optional and only affects AC circuits when power factor is below 1.
Drop, voltage at the load, and comparison against your limit.
The estimated drop exceeds the design limit of 3.0%. Voltage at the load lands at roughly 222.1 V.
This bar only compares the calculated drop with the configured limit — it isn't ampacity or code compliance.
Among the standard sections compared, 6 mm² is the first that keeps the drop within the chosen limit.
In single-phase, the tool accounts for the round trip. Resistance is estimated from copper's resistivity corrected to 20 °C.
Fill in the values, paste your text, or upload the file this tool works with.
Most tools update live as you type; a few use a single button. Either way, the result appears right on this page.
Copy, download, or share what the tool produces — you're always in control of the output.
The Voltage Drop Calculator is a tool for estimating voltage loss along a single-phase, three-phase, or DC cable run from current (or power), length, material, cross-section, and conductor temperature — including power factor and reactance for AC circuits — and it recommends the first standard cable section that keeps the drop within your chosen limit.
Pick the circuit type, enter the load as current or power, the one-way length, the material, and the cable cross-section to see the drop in volts and as a percentage, the estimated voltage at the load, and the first standard section that meets your design limit.
"One-way length" is always the distance from source to load, never round-trip — the tool applies the factor for the circuit type you chose on its own.
ΔV = 2 × I × L × ρ(T) / SΔV = 2 × I × L × (R·cosφ + X·sinφ)ΔV = √3 × I × L × (R·cosφ + X·sinφ)In "Current" mode, type the measured or design current directly in amps. In "Power" mode, enter the active power (W), the source voltage, the power factor (cos φ), and the efficiency (η) — useful when all you have is a piece of equipment's rated power, such as a motor's nameplate, instead of a measured current; the tool estimates the equivalent current before calculating the drop. The voltage shortcuts (127, 220, 230, 380, 400, and 440 V) fill in the most common single-phase and three-phase supply voltages.
Power factor (cos φ) and the approximate reactance (Ω/km, under "Technical adjustments") only affect single-phase and three-phase circuits, and only when the power factor is below 1 — in that case the drop adds a resistive and a reactive share. Direct current locks the power factor to 1 automatically once you switch the circuit type, and leaving reactance at 0 Ω/km makes the calculation use only the resistive drop.
The copper or aluminum resistivity used in the calculation is corrected from the conductor's operating temperature entered under "Technical adjustments" (20 °C by default, adjustable from -20 °C to 150 °C) — a hotter conductor has more resistance, and for the same current, more voltage drop.
The "First standard section that meets the limit" card evaluates a list of commercial cross-sections, from 1.5 to 240 mm², under the same current, length, material, and temperature you entered, and flags the first (smallest) section whose drop stays within your configured design limit — alongside a comparison of the standard sections closest to the one you typed, marking which ones meet the limit. If no section up to 240 mm² qualifies, the tool says so instead of suggesting a value.
The "Design limit" is adjustable from 0.1% to 20% (3% by default) because design criteria and codes vary by country, circuit type, and application. The margin bar only compares the calculated drop against that limit — the "comfortable margin", "tight margin", and "review the section" states don't represent the cable's current-carrying capacity or compliance with any specific code.
The calculation runs entirely in your browser from the values you enter — nothing is sent to a server. Voltage drop is only one variable in an electrical design: the cable's current-carrying capacity, ambient temperature, installation method, circuit grouping, short-circuit protection, and local codes also need to be checked by a professional before any installation is approved.
Use Current when you know the circuit's measured or design current. Use Power when all you have is the equipment's rated power — for example, on a motor's nameplate — along with the power factor and efficiency; the tool estimates the equivalent current before calculating the drop.
Each uses a different formula: single-phase and DC apply a factor of 2 (current travels out and back through the conductor); three-phase uses a factor of √3, reflecting how line-to-line voltage relates to per-phase current in a balanced load. In DC, the power factor is always locked to 1.
Always one-way — from source to load. The tool applies the round-trip factor (single-phase or DC) or the √3 factor (three-phase) on its own; don't double the value yourself.
Only in AC circuits (single-phase or three-phase) and only when the power factor is below 1. With reactance at 0 Ω/km or the power factor at 1, the calculation uses only the resistive drop.
Because a conductor's resistance rises with temperature. The tool corrects copper or aluminum resistivity from the temperature you enter (20 °C by default); a hotter conductor has more resistance, and for the same current, more voltage drop.
The tool tests a list of standard gauges (from 1.5 to 240 mm²) under the same current, length, material, and temperature, and flags the first (smallest) section whose drop stays within your configured limit — it isn't necessarily the technically ideal gauge for current-carrying capacity or short-circuit withstand, only for voltage drop.
Copper, for the same cross-section — it has roughly 60% of aluminum's resistivity at 20 °C, so a copper run of the same gauge drops noticeably less voltage than an aluminum one.
No. It calculates voltage drop only; the cable's current-carrying capacity, grouping, ambient temperature, short-circuit protection, and local codes also need to be checked by a professional before any real installation.
Calculate true 3D printing costs and sale prices including filament, energy, and labor.
Calculate tiles and boxes needed for a floor.
Size a solar panel system.
Estimate how long a battery will last.
Slab, beam, column, or footing, in m³, liters, or bags.
Estimate liters, cans, and cost for painting.
Convert roof slope and estimate rafters and surface area.
Estimate decking, framing lengths, and fasteners.
Enlarge images with profiles tuned for their content.
Run a live TLS handshake against a domain and grade its certificate, chain, and protocol support.